Project 03 / Heat rejection · Urban wind
ICON Oceania AC Condenser Heat Re-Ingestion CFD Study
Stacked condenser performance tested through an eleven-level urban canyon.
- Location
- 499 Kent Street, Sydney, NSW
- Project context
- High-rise residential tower · Engineering consultant: Confidential
499 Kent Street hospitality render
Headline result41.9 °C maximum inlet
VerifiedLevels 8–18
Verified35 °C ambient
Verified24 kph wind
The study
Vertical plume interaction quantified from Level 8 to Level 18.
Challenge
Corner-mounted condenser plants discharge beside neighbouring buildings, creating a credible risk of hot-air re-ingestion at the same and higher levels.
Method
The external model included the tower corner, adjacent buildings and all condenser plants operating at full load under 35 °C ambient temperature and a 24 kph design wind.
Outcome
Warm-plume interaction increased with height, but every monitored inlet remained inside acceptable operating limits; lower levels stayed close to ambient.